Send us your questions/comments

The problems with base tanks can include: (a) larger tanks raise the working level of the generator where steps and walkways can be required for routine inspection and maintenance, (b) the fuel tanks are subject to a higher level of vibration due to the construction within the generator frame, and (c) the large flat bottoms of the tanks with internal baffle construction, can promote biological growth within the tank.