Send us your questions/comments

Required accessories for tank fill systems are as follows:
(a) tight fill connection for delivery hoses which are usually camlock type connections to minimize spills.
(b) spill containment devices surrounding the fill pipe connection to the delivery hose.
(c ) overfill prevention valve in the fill pipe. This would be either a mechanically actuated float type valve, or an electrically actuated valve that closes at 90% fill level.
(d) high level sensors in the fuel tank for high level alarm activation.
(e) a high level alarm device providing visual and audible indication.
(f) a means of determining the fuel level in the tank such as an electronic level gauge.
(g) a secondary means of determining the fuel level in the tank such as a manual gauge port.
(h) safety equipment including spill cleanup kits and fire extinguishers.
(i) manual shutoff valves and check valves for aboveground tank systems.