12.05 How is a Red Jacket pump controller integrated into a fuel system?

The basic Red Jacket pump controller allows for a 120 VAC input signal (which they call a hook signal) to activate the submersible pump. The Earthsafe duplex pump controller activates the controllers by providing this signal.

The basic Red Jacket controller provide motor protection, but lacks the following features that are often required of mission critical systems:

  • local power disconnect switch
  • manual mode switch in addition to its passive auto mode
  • current sensor or other feedback demonstrating pump function.