Local regulations may require fire protection for fuel piping in buildings where it is routed outside special rooms such as generator rooms, boiler rooms, and tank storage rooms. Typically 2 hour fire protection is required.
A typical method of providing the fire protection is by insulating the pipe with fire rated insulation.
A common alternative method is to route the piping through fire rated shafts which are often provided for utility risers in multi-story building.
Either method prevents visual inspection of the piping, so double contained pipe with leak detection is typically used.