26.04 What are the special requirements for underground tanks in California?
California regulations include:
- Pre-qualification approval of all equipment and materials used in underground fuel tank systems.
- Full secondary containment of all tanks and piping.
- Fill pipes and spill container located within secondary containment sumps. All tank openings including tank gauging within secondary containment sumps.
- Periodic testing of secondary containment piping, sumps, tanks, and tank monitors.
- Double wall construction for tank sumps and piping transition sumps.
- Double containment of vent piping.
- Continuous positive monitoring of tank, pipe, and sump secondary containment by vacuum, pressure, or hydrostatic method.
- Precision leak detection testing after installation and backfill using tracer gas method.